Parallel Linear Actuator Synchronization: An OEM Engineering Guide to Dual-Hall Pulse Counting, Anti-Racking Safety, and Multi-Column Load Sharing
2026/11/07

Parallel Linear Actuator Synchronization: An OEM Engineering Guide to Dual-Hall Pulse Counting, Anti-Racking Safety, and Multi-Column Load Sharing

Specify parallel linear actuator synchronization: compare Hall feedback and servo control, screen skew and load sharing, and prepare an OEM RFQ checklist.

Published: November 7, 2026. Content and source review: November 7, 2026. Scope: Global OEM engineering and procurement teams specifying electromechanical multi-actuator systems; English-language guidance using SI units.

Executive conclusion: Parallel linear actuator synchronization requires a defined position relationship between axes. Sharing a DC supply or relay command does not establish that relationship. On a rigid lifting frame, unequal travel can create tilt, binding, and overload. Choose a mechanical linkage or a closed-loop controller, specify allowable mismatch at the load, and validate stopping behavior under asymmetric loads. Dual-Hall feedback is one option; direct linear sensing and servo systems may suit other requirements. Equal position does not prove equal load sharing.

Evidence boundary: The calculations below are illustrative engineering screening examples, not measured product performance or customer test results. Manufacturer pages establish available control concepts; they do not substantiate the example tolerances or certify this site's products. Final limits depend on frame stiffness, mounting geometry, drive ratings, feedback configuration, and application risk assessment. Medical devices, personnel lifts, and other regulated equipment require their own applicable standards and validation.

For an initial specification review, send your load, stroke, speed, span, and allowable skew in an engineering RFQ. Use the side-load and radial-force guide and column-buckling guide to define the mechanical constraints first.

Two-output actuator controller enclosure with channel indicators and synchronization adjustment

Figure 1: Controller reference image. Confirm feedback inputs, channel ratings, firmware behavior, and safety documentation for the exact supplied model; the image does not establish these capabilities.


1. The Engineering Trap: Why Direct Parallel Wiring Fails

In industrial automation, heavy medical patient tables, solar tracking arrays, opening roof hatches, AGV scissor lifts, and multi-column ergonomic workstations, lifting loads with two or four synchronized linear actuators is a common mechanical requirement. A shared 24 V or 48 V power bus does not ensure that two nominally identical actuators extend and retract at the same speed.

The Physics of Speed Discrepancy in DC Motors

For a brushed permanent-magnet DC motor at approximately steady speed, a simplified relationship is:

omega = (V_applied - I * R_armature) / k_e

Here omega is rotational speed in rad/s, V_applied is motor-terminal voltage, I is armature current, R_armature is winding resistance, and k_e is the back-EMF constant. This approximation omits brush drop and transient inductance; a BLDC drive requires its own commutation and control model.

Winding resistance, magnet strength, gearbox friction, and cable voltage drop can vary between units. Do not assume a universal percentage mismatch from these effects. Ask for the exact actuator's load-speed curves and pair-to-pair variation over your operating temperature and voltage range. A no-load matching result alone cannot establish loaded synchronization.

The Compounding Effect of Asymmetrical Loading

Center-of-gravity offsets, payload changes, and mounting friction can produce different axial loads. As an illustrative static case, a 10,000 N platform load split 65/35 gives reactions of 6,500 N and 3,500 N before acceleration, friction, or linkage effects. The more heavily loaded brushed DC actuator generally needs more current and may run slower at the same terminal voltage.

For a separate travel example, assume constant speeds of 10 mm/s and 9 mm/s for 20 seconds. The axes move 200 mm and 180 mm: a 20 mm stroke mismatch. This is arithmetic from assumed inputs, not a claimed manufacturing tolerance. A compliant mechanism may accommodate some mismatch, while a rigid assembly may bind much earlier. Direct parallel wiring therefore cannot be accepted as proof of synchronized travel.


2. Kinematic Racking Geometry and Structural Binding Mechanics

When multiple linear actuators are mechanically tied to a shared platen, crossbar, or scissor linkage, stroke divergence can create bending moments and side loads, depending on joint freedom and the external guide arrangement.

Parallel actuator skew geometry and feedback-control selection framework; example parameters require application validation

Figure 2: Kinematic racking geometry, dual-Hall pulse counting closed-loop control architecture, and multi-axis OEM sourcing decision framework.

Mathematical Derivation of Angular Skew

For two vertical axes, define W as the horizontal distance between their load attachment points and Delta_h as their height difference. If the beam between those points is treated as rigid, its tilt is:

theta_skew = arctan( Delta_h / W )

For small angles, theta_skew ≈ Delta_h / W, with the angle in radians. This geometry describes beam tilt, not the force distribution or the allowable guide misalignment.

Side Load Depends on Mounting Geometry

Beam tilt alone does not determine rod side load. A freely pivoting clevis can rotate with the load, whereas a rigidly restrained rod and misaligned guides can develop substantial lateral reactions. For a known transverse tip force F_side acting at unsupported lever arm L, the simplified bending moment is:

M_bending = F_side * L

Use meters for L to obtain N·m. Do not substitute the actuator's full retracted body length for the unsupported rod length. If the actual force direction is known to be at angle alpha to the rod, its transverse component is F * sin(alpha); alpha is not automatically equal to the crossbeam tilt angle.

Binding Cannot Be Predicted from Skew Alone

Guide clearance, bearing spacing, lubrication, frame stiffness, and joint constraints determine the reactions and friction. There is no universal bushing jam angle or friction multiplier for all actuator assemblies. Obtain allowable misalignment and moment ratings from the guide and actuator suppliers, then measure load-point displacement and motor current on the assembled prototype.

A stalled axis can overheat, damage its drive train, or force the remaining axes to overload the structure. The controller should detect loss of motion and stop the group within a validated envelope. Motor overcurrent protection alone may act too late to protect a stiff frame with a small allowable displacement error.


3. Comprehensive Comparison of Multi-Actuator Synchronization Architectures

Choose the architecture using allowable mismatch, speed, load asymmetry, mechanical packaging, and fault response. The six options below compare selection constraints, not guaranteed accuracy bands. No interface name establishes a maximum span or a system cost multiplier.

Synchronization architectureWhat establishes the relationshipUseful selection caseLimit or fault to investigateEvidence to request
Direct electrical parallel, open-loopShared voltage and command onlyIndependent mechanisms where relative travel is not criticalUnequal loaded speeds; no active position correctionFull-stroke mismatch measurements and a mechanism-specific justification
Mechanical cross-shaft or linked screw jacksShared mechanical driveSeveral lifting points with room for shafts and gearboxesShaft twist, backlash, alignment, and critical speedTorsional calculation and loaded travel measurements
Current-balancing controlMotor current used as a load proxyLoad monitoring or assistance to another feedback loopEqual current does not establish equal displacementDirect position measurements under asymmetric load
Dual-Hall incremental feedbackCalibrated counts and a coordinated controllerDC actuator groups with a defined homing methodCount loss, gearbox compliance, and power-loss recoveryCount definition, mismatch logs, and fault-response records
Direct linear position feedbackSensor measures rod or load-point positionApplications needing downstream position observationSensor mounting, linearity, wear, and reference integrityInstalled accuracy budget and calibration method
Coordinated servo motionTrajectory control with suitable drives and feedbackDynamic multi-axis motion with tighter tracking requirementsNetwork timing, drive following error, and feedback locationExact motion mode, timing configuration, and loaded tracking results

CANopen, EtherCAT, and IO-Link provide different communication mechanisms; they are not interchangeable guarantees of synchronized motion. Confirm the supported motion profile, update timing, and controller function for the selected drives. LINAK's Integrated Controller overview documents built-in electronics and interface options, not a universal synchronization accuracy specification.


4. Dual-Hall Quadrature Pulse Counting: How Electronic Synchronization Operates

Dual-Hall pulse counting can provide relative position feedback for coordinated DC actuators. Whether it meets your requirements depends on the decoded count density, mechanical error, controller bandwidth, and the recovery strategy after lost position.

Two heavy-duty rod-style linear actuators shown as a paired configuration

Figure 3: Paired-actuator reference image. Appearance does not verify matching, Hall feedback, ingress protection, or suitability for synchronized lifting; request the exact model documentation.

Sensor Mechanics: Rotor Pole Wheels vs. Output Screw Tracking

Two Hall outputs may be arranged in electrical quadrature, but the term “dual Hall” alone does not prove their phase relationship or decoding convention. Request the waveform definition and supported controller input circuitry. A motor-side sensor observes rotation before gearbox backlash, screw compliance, and mounting deflection; count resolution is not load-point accuracy.

Define the terms before calculating count density:

C_motor = cycles per motor revolution on one Hall channel
q = controller decoding factor: x1, x2, or x4
i = motor revolutions per screw revolution
lead = rod travel per screw revolution in mm
R = (C_motor * q * i) / lead   [decoded counts/mm]
x = (count - count_at_home) / R

For an illustrative motor with 4 cycles per revolution on one channel, x1 decoding, a 30:1 reduction, and 4 mm screw lead, R = 30 counts/mm, or about 0.033 mm per count. With x4 decoding the same example yields 120 counts/mm. Neither value establishes mechanical accuracy. Do not confuse magnetic poles, pole pairs, signal cycles, and decoded edges in a purchase specification.

Quadrature can reveal direction from A/B phase order. Invalid state transitions can identify some faults, but valid-looking noise and missed cycles can still corrupt position. Shielding, input filtering, signal levels, and maximum input frequency must be verified on the installed cable harness.

Master-Follower and Virtual-Master Control

A simple follower that cannot slow its leader may lose tracking when the follower reaches its torque or speed limit. A coordinated master-follower design can avoid this by limiting or stopping the whole group. A virtual-master design instead provides a shared reference trajectory and constrains each axis against it. The name of the algorithm alone does not establish fault tolerance.

For two axes with calibrated positions, define:

error_mm = x_1 - x_2

Only compare raw counts when both axes share the same count scale and mechanical datum. A controller can slow the leading axis and reduce group speed when one axis approaches its available thrust. If an axis stalls or feedback becomes implausible, it should enter a defined group-fault response rather than continue chasing an unreachable position. Deadband, acceleration, output limits, and anti-windup settings need loaded testing. Level travel remains subject to the approved mismatch envelope.

If you need help turning these terms into a purchasing specification, request a feedback and controller compatibility review with the actuator ratio, screw lead, signal type, and operating speed.


5. Calibration, Homing, and Error Recovery Protocols

Incremental counts need a known datum. Lost pulses, movement while control power is absent, or a slipping coupling can invalidate the estimated position. Equal stored counts do not establish that the frame is level.

Supplier-Approved Homing

Use the exact actuator/controller manufacturer's permitted reference method: dedicated reference switches, verified end-limit signals, an absolute sensor, or expressly approved current-limited stop detection. Driving into a mechanical hard stop is not a universal homing procedure. A current rise can indicate an obstruction anywhere in the stroke; an internal limit switch may interrupt current before any stall signature appears.

A commissioning sequence should document the following decisions:

  1. Support and secure the load, clear the travel zone, and confirm that referencing will not exceed allowable frame tilt.
  2. Establish which datum signal is valid for each axis and how reference-signal faults are detected.
  3. Move at an approved homing speed while monitoring group mismatch, current, time, and travel limits.
  4. Stop each axis according to the approved procedure. Independent referencing is permissible only when the mechanical assembly can accommodate it.
  5. Verify physical alignment against an independent measurement before accepting the coordinate origins.
  6. Save the calibrated state with an integrity check, and document when it becomes invalid.

Do not adopt generic current thresholds, stall dwell times, relief strokes, or cycle intervals. These depend on end-stop capacity, load, motor heating, and allowable skew. A current-sensing method needs explicit approval for the supplied hardware and evidence that an obstruction cannot be mistaken for a valid home.

Emergency Stops and Power-Loss Recovery

Axes may coast or backdrive differently after power loss. Non-volatile count storage can preserve the last recorded estimate, but cannot record unobserved movement after sensor power disappears. A memory checksum validates stored data integrity, not actual position.

Inhibit automatic restart until the controller has established a trustworthy position state and the machine's restart conditions are met. Recovery may require supported-load inspection, independent position measurement, or a supervised reference sequence. Do not force a full retraction merely because count integrity is uncertain: the recovery movement itself must remain within the mechanical and safety envelope.


6. Functional Safety, Anti-Racking Cutoff, and Compliance Standards

Separate normal synchronization from any safety function required to prevent hazardous tilt, crushing, or falling loads. ISO 13849-1:2023 provides a framework for safety-related control-system design. It does not assign a universal skew threshold or required performance level to parallel actuators. Determine the required safety function and performance level from the machine risk assessment and applicable product standards; sensor diagnostics alone do not establish PLc or PLd.

Derive a Trip Window with Stopping Margin

The geometric relationship can translate an assumed angular limit into a height limit:

Assumed span W = 1,200 mm
Assumed angle limit = 0.5 degrees
Geometric height limit = W * tan(0.5 degrees) = 10.47 mm

The assumed 0.5-degree value is not a guide rating or a recommended safe limit. Use the smallest permitted displacement from the frame, guide, joint, and load constraints. Trigger a fault before reaching that limit, allowing for measurement error and the additional mismatch accumulated during detection and stopping:

trip_mismatch + uncertainty + additional_stopping_mismatch
    <= allowable_physical_mismatch

For a separate illustrative error budget, suppose the approved physical limit is 4.0 mm, combined uncertainty is 0.8 mm, and measured worst-case additional mismatch during response is 1.2 mm. The trip setting must be no greater than 2.0 mm before any further required design margin. At 5 decoded counts/mm this is 10 counts. These inputs are hypothetical; determine stopping mismatch under the worst credible load, direction, speed, and brake condition.

Define the Entire Group-Fault Response

A fault response must address controlled deceleration or power removal, gravity-load retention, brake sequencing, upstream interlocks, and deliberate reset. Setting PWM to zero does not itself prove a safe stop or load holding. A spring-applied brake may engage when de-energized, but its timing and load rating must be verified. An emergency stop, a synchronization trip, and a motor overload alarm need distinct documented functions even if some hardware is shared.

Check open and shorted sensor leads, stuck channels, implausible direction, missing motion, controller resets, and loss of communication. A pulse timeout must exceed the longest legitimate interval between edges at the slowest commanded speed while remaining short enough for the permitted stopping envelope. Test faults in a guarded setup with supported loads. Request the required safety-system analysis and validation records separately from ordinary functional test logs.


7. OEM Buyer Action Checklist & Sourcing Inspection Protocol

A multi-axis RFQ needs system-level acceptance criteria, not just the single-actuator thrust rating. Ask vendors to quote the actuator group, controller, harness, power supply, referencing method, and validation deliverables together. Thomson's linear actuator selection overview identifies load, travel, power, control, and environment as selection inputs; those inputs must also be checked for the coupled assembly.

OEM Synchronous Actuator RFQ Specification Matrix

Use this matrix to agree application-specific requirements. The entries are evidence requests, not claimed capabilities of the pictured products.

Engineering parameterRFQ input to provideAcceptance boundary to agreeVerification record
Load per axisTotal moving mass, center of gravity, linkage geometry, accelerationEach axis stays within force, buckling, and duty-cycle limitsReaction calculation and loaded current/force records
Motor and drive compatibilityVoltage range, peak current, target speed, temperatureAdequate control headroom at the worst operating pointExact-model load-speed curves and drive ratings
Feedback count definitionSignal voltage, cycles/revolution, decoding, ratio, screw leadCount scale and frequency compatible with controllerPinout, waveform capture, and measured travel calibration
Loaded position mismatchMaximum allowed load-point differential over the strokeError envelope including backlash and deflectionIndependent displacement measurements versus controller counts
Fault responsePermitted displacement after a fault and restart rulesTrigger and stopping budget within mechanical limitsTime-aligned position, current, fault, and brake traces
Cabling and EMCCable length, routing, environment, grounding arrangementReliable feedback under representative motor switchingHarness drawing and interference/fault test results
Homing and recoveryApproved datum, support conditions, power-loss scenarioNo unapproved hard-stop loading or automatic unsafe restartSupplier procedure and witnessed recovery tests
Environmental protectionTemperature, dust, water exposure, connector mating stateRequired ingress protection for the installed assemblyApplicable test report and installation restrictions

Multi-Column Load Sharing: Position Is Not Force

For two vertical supports in a simplified static beam model, with total downward load F at distance a from support 1 and support spacing W:

Reaction_1 = F * (W - a) / W
Reaction_2 = F * a / W

A centered load gives equal reactions only under the model's assumptions. Add the moving structure's own weight, acceleration, friction, and linkage effects when sizing the real system. A synchronized pair can hold equal extension while carrying very different forces.

Four rigid supports introduce stiffness-dependent load distribution. Equal corner height cannot prove that each actuator carries 25% of the payload. Guide preload, assembly tolerances, and frame compliance can overload one corner. Specify a structural model and instrumented load validation; where necessary, use force sensing or a mechanically equalizing arrangement. A position loop and a load-sharing loop need compatible objectives and limits rather than independent commands that fight each other.

The 8-Point OEM Procurement and Quality Checklist

  • 1. Define the assembly: Record stroke, speed, moving load, center-of-gravity range, span, guide arrangement, and duty cycle.
  • 2. Verify each axis rating: Check the highest credible reaction rather than dividing total load by the number of actuators.
  • 3. Confirm feedback compatibility: Obtain pinouts, count conventions, signal levels, input-frequency limits, and the mechanical datum definition.
  • 4. Agree a loaded mismatch envelope: Measure at the load points with independent instruments; include asymmetric loading and both travel directions.
  • 5. Validate group stopping: Log detection latency and additional mismatch, including brake behavior and restart inhibition.
  • 6. Qualify the harness: Follow the drive manufacturer's EMC and shield-bonding instructions; do not impose a universal one-end-only shield rule.
  • 7. Approve referencing and recovery: Test the permitted homing procedure and interrupted-power cases without assuming stored counts prove position.
  • 8. Control production changes: Tie acceptance records to actuator, controller, harness, firmware, and calibration revisions.

Step-by-Step Buyer Action Plan by Deployment Phase

Before RFQ: Freeze the allowable load-point error and force envelope with the machine designer. Identify who owns mechanical calculations, controller integration, and safety validation. Compare quoted system scope, engineering effort, required test records, service access, and replacement parts; a cheap actuator without the required controls is not a comparable quotation.

Prototype qualification: Test no-load, nominal-load, and worst credible eccentric-load conditions over the required speed and temperature range. A 70/30 split may be a useful selected test case for a two-axis assembly, but is not a universal qualification standard. Use calibrated independent displacement sensors and record count positions, terminal voltage, current, and time together. Specify repetitions and acceptance rules before running the test; do not represent a proposed protocol as completed testing.

Commissioning: Check guide and pin alignment to drawing tolerances, establish approved reference positions, and verify fault wiring. Follow the agreed assembly sequence with mechanical support in place. Validate shield terminations against the actual drive and EMC design, including chassis bonding and cable routing. Confirm the final harness length and power supply match the qualified setup.

Production and maintenance: Retain serialized acceptance results and configuration versions. Define recalibration triggers from observed drift, service events, reference faults, and supplier guidance rather than an arbitrary daily or 50-cycle schedule. Repeated synchronization trips warrant inspection of the frame, guides, wiring, and drive headroom before changing trip limits. Replacing one axis may require recalibration or requalification of the group.


8. Frequently Asked Questions (FAQ) for OEM Engineers & Buyers

Q1: Can one DPDT relay synchronize two linear actuators?

A shared relay can command both motors, but provides no position correction. Use it only where the mechanism permits the resulting independent travel and the electrical switching ratings are suitable. A rigid assembly with a specified mismatch limit needs a validated mechanical or electronic synchronization method.

Q2: Does dual-Hall feedback eliminate counting errors?

No. Correctly arranged quadrature signals can identify direction and some invalid transitions. Missing cycles, plausible noise, or movement while sensing is unpowered can still invalidate position. Confirm the actual Hall phase relationship and decoding method rather than inferring them from the number of sensor wires.

Q3: What synchronization accuracy should we specify?

Start with allowable mismatch at the supported load and the available stopping margin. Then budget count quantization, calibration, backlash, deflection, sensor error, and dynamic following error. Ask for measured performance under your operating conditions. A count resolution of 0.033 mm does not establish 0.033 mm installed accuracy, and a fieldbus label does not establish a tighter result.

Q4: Why does a system work unloaded but trip under payload?

Possible causes include guide binding, uneven reactions, insufficient motor thrust, supply voltage sag, controller current limits, and feedback interference. Compare independent displacement with counts and terminal voltage/current traces. Use the side-load mitigation guide to review mounting reactions; do not raise the trip limit until the cause is established.

Q5: How often should a synchronized system home?

Follow the qualified reference strategy. Homing may be required after commissioning, service, loss of position confidence, or a defined maintenance trigger. There is no universal cycle interval. A full retract-to-stop movement is acceptable only when the supplier permits it and the machine can perform it safely with its actual load.

Q6: Can four or more actuators share one controller?

Yes, if the controller and firmware explicitly support the group size, feedback inputs, channel currents, coordinated trajectory, and group-fault behavior. A box with four outputs is not necessarily a four-axis synchronizer. Verify both maximum corner mismatch and per-axis force; keeping corners level does not ensure equal load sharing.


9. Authoritative Sources & Regulatory References

These public pages were checked on November 7, 2026. Standard abstracts establish scope; manufacturer pages describe their own offerings. None supplies measured results for the illustrative examples or certifies the products pictured here.

  1. ISO 13849-1:2023 — Safety-related parts of control systems, general principles for design. ISO publication record and abstract. Supports the safety-design scope; it does not prescribe an actuator skew setting or application-specific required performance level.
  2. Thomson — Linear Actuators: Types, Benefits and Selection Guide. Manufacturer product and selection overview. Supports selection inputs and the availability of customized control and synchronization options, not generic precision bands.
  3. LINAK — Linear actuators. Manufacturer actuator overview. Describes selected integrated-control products with position feedback, parallel movement, and communication options; applicability depends on model and configuration.
  4. LINAK — IC Integrated Controller. Manufacturer integrated-controller overview. Describes built-in H-bridges, monitoring, and interfaces; it is not a certification or performance guarantee for third-party controllers.

10. Partner with Engineering for Matched Synchronous Actuator Systems

Bring the mechanical and controls requirements together before selecting individual actuators. Request an engineering RFQ review with axis count, stroke, speed, load and center-of-gravity range, span, allowable load-point mismatch, supply voltage, duty cycle, operating environment, and power-loss holding requirements.

Ask the supplier to return an exact-model bill of materials, controller compatibility statement, feedback definition, approved homing procedure, and proposed loaded acceptance test. Agree which matching, calibration, sealing, and safety deliverables are included in the quotation. Do not treat reference images as evidence that those options are already supplied or validated.

For component discussion, the dual-output controller reference image and four-channel DIN-rail controller reference image show enclosure concepts only. Continue mechanical screening with the column-buckling guide and ball-screw versus roller-screw sourcing guide.

Review this specification when the load, guide geometry, firmware, harness, or safety requirements change, and recheck sources before reusing the guide in a new design release.

Author

avatar for Malcolm Fraser - Senior Mechatronics & Linear Motion Specialist
Malcolm Fraser - Senior Mechatronics & Linear Motion Specialist
1. The Engineering Trap: Why Direct Parallel Wiring FailsThe Physics of Speed Discrepancy in DC MotorsThe Compounding Effect of Asymmetrical Loading2. Kinematic Racking Geometry and Structural Binding MechanicsMathematical Derivation of Angular SkewSide Load Depends on Mounting GeometryBinding Cannot Be Predicted from Skew Alone3. Comprehensive Comparison of Multi-Actuator Synchronization Architectures4. Dual-Hall Quadrature Pulse Counting: How Electronic Synchronization OperatesSensor Mechanics: Rotor Pole Wheels vs. Output Screw TrackingMaster-Follower and Virtual-Master Control5. Calibration, Homing, and Error Recovery ProtocolsSupplier-Approved HomingEmergency Stops and Power-Loss Recovery6. Functional Safety, Anti-Racking Cutoff, and Compliance StandardsDerive a Trip Window with Stopping MarginDefine the Entire Group-Fault Response7. OEM Buyer Action Checklist & Sourcing Inspection ProtocolOEM Synchronous Actuator RFQ Specification MatrixMulti-Column Load Sharing: Position Is Not ForceThe 8-Point OEM Procurement and Quality ChecklistStep-by-Step Buyer Action Plan by Deployment Phase8. Frequently Asked Questions (FAQ) for OEM Engineers & BuyersQ1: Can one DPDT relay synchronize two linear actuators?Q2: Does dual-Hall feedback eliminate counting errors?Q3: What synchronization accuracy should we specify?Q4: Why does a system work unloaded but trip under payload?Q5: How often should a synchronized system home?Q6: Can four or more actuators share one controller?9. Authoritative Sources & Regulatory References10. Partner with Engineering for Matched Synchronous Actuator Systems